Azoline test
Published by Moslem Salesi Mousaabadi, Industrial water consultant at Mohafez Shimi
Tags
- Treatment
- Testing Kit
Published by Moslem Salesi Mousaabadi, Industrial water consultant at Mohafez Shimi
I use 20 ppm for the protection of copper ans brass in a closed loop, about the same cycled up in a cooling tower. Tolytriazole is my choice, or a blend of azoles depending upon the system being treated. Some think 20 ppm is high, but sometimes I use more. The object is to protect the system, not save on chemical costs.
Published by Waymon Hofheins
I agree with Waymon
Published by Ahmed Soorma, General Manager at Soorma & Sons