Distance between two Valves in a same chamber in a Water Transport Network

Published by

We have a chamber in the Water Transportation and Distribution Network where there are two/three valves. Is there any specific standard that defines the size of the chamber and the distance between the valves in the chamber itself plus distance from the wall of chamber?

Tags

7 Answers

No specific standard that I ...

No specific standard that I have ever come across, chambers tend to be build to ensure the assets are centralised and operable. One thing to always consider when working on the valves in a large chamber is thrusting and the stability of pipework as this can be compromised depending on the installation methods, pipe design, materials and work being completed

Published by

Let me add for  a DN100 size ...

Let me add for  a DN100 size valve

Published by

300mm make-up piece between ...

300mm make-up piece between the valves

Published by

2 Comments

can you please share the standard from which you have derived this or is it best engineering practice? 

Published by

Permalink

As regards the size of the ...

As regards the size of the chamber, if it is merely a distribution point en-route, the size ranges from 2 minuits' to 5 minuites retention period i.e. capacity to accomodate the discharge received in 2 minutes to 5 minutes. For valves there should be no specific criteria in my opinion. 

Published by

As regards the

As regards the 

Published by

As regards the

As regards the 

Published by

Il y a deux éléments qui ...

Il y a deux éléments qui agiront sur les dimensions de votre chambre et les espacements entre les vannes : i) les gabarits (size) des vannes et les espaces nécessaires à leurs manutention, et ii) le poids éventuels des vannes qui conditionneront les dimension génie civil des bâtis sur lesquels elles seront posées.

Published by

1 Comment

Say one main branch 300 mm dia meter branching off to DN 200 and DN 250 with individual valves to shut off. You need 2 Nos thrust type dismantling joints of sizes DN 200 and DN 250  plus two gate valves of size DN 200 and DN 250 in the chamber. 150 mm spacing between flanges to wall. Hence you need  about 2000 x1200 chamber.