The vent shall be reverse"J" ...
Published by Govindasamy Manickam, GM at Adani Power Ltd.
The vent shall be reverse"J" type with back fire arrester since the tank contains H2 gas also. The size of the vent to be engineered to meet the purging air flow.
1 Comment
Can you recommend vent vendors who can meet our requirements?
Published by Hilal Alkhozaimi, Project Manager at Majis Industrial Services SAOC, Majis