Good Morning Navis,
Considerations for additional info as follows;
a) Is there any source water pretreatment ?
b) Rust is indicative of iron. What is the iron value ?
c) The 8.5 pH will cause the calcium and magnesium to scale. Are you adding anti scaling chemical ?
d) You advise chlorine is .5-1ppm. Are you chemical injecting chlorine, and if so, what type ?
e) Normally pH values reported will not cause corrosion. Do you mean deposition ?
f) Outside of noticing the rust etc, what if any are the negative effects ?
g) Periodic blow down / drain / refill may all that is needed.